A. The following sections of the International Mechanical Code, 2018 Edition, are amended to read as follows:

1. Section 101.1 Title is amended by adding the name "Town of Breckenridge."

2. Section 103.2 Appointment is amended to read exactly as set forth in IBC Section 103.2 as amended.

3. Section 103.3 Deputies is amended to read exactly as set forth in IBC Section 103.3 as amended.

4. Section 103.4 Liability is amended to read exactly as set forth in IBC Section 104.8 as amended.

5. Section 106.4.3 Expiration is amended to read exactly as set forth in IBC Section 105.5 as amended.

6. Section 106.4.4 Extensions is deleted in its entirety.

7. Section 106.5.2 Fee Schedule is amended to read as follows:

106.5.2 Fee Schedule. The fees for mechanical work shall be in accordance with the Town of Breckenridge Building Permit and Inspection Fee Schedule as set forth in IBC Section 109.2 as amended.

8. Section 106.5.3 Fee Refunds is amended to read as follows:

106.5.3 Fee Refunds. The building official is authorized to establish a fee refund policy.

9. Section 107.2 Required inspections and testing is amended by adding a new subsection, 107.2.6 Re-inspections, to read as follows:

107.2.6 Re-inspections is to read exactly as set forth in IBC Section 110.7 as amended.

10. Section 108.4 Violation penalties is amended to read exactly as set forth in IBC Section 114.4.

11. Section 108.5 Stop work orders is amended to read exactly as set forth in IBC Section 115.

12. Section 109 Means of appeal is deleted in its entirety and reenacted to read exactly as set forth in IBC Section 113.

13. Section 202 Definitions is amended by adding the following definitions within the alphabetical order of the existing definitions:

CERTIFIED SOLID FUEL BURNING DEVICE: A solid fuel burning device that is certified by the Air Pollution Control Division of the Colorado Department of Health or approved by the building official as meeting the emission standards set forth in Section IV of Regulation No. 4 of Volume I of the Colorado Air Quality Control Commission (EPA Phase II or III).

SOLID FUEL BURNING DEVICE: Any fireplace, stove, firebox, or other device intended and or used for the purpose of burning wood, coal, pulp, paper, pellets or other non-liquid or non-gaseous fuel.

14. Section 301 General is amended by adding a new subsection, 301.19 Floor Drains, to read as follows:

301.19 Floor Drains. All mechanical rooms (furnace, boiler, water heater rooms) shall be provided with a floor drain.

15. Section 509.1 Where required is amended by adding the following paragraph.

All fire suppression systems required by this code shall be inspected and approved by a special inspector. The special inspector shall be an authorized representative of the RWB fire department.

16. Section 701.1 Scope is amended by adding a new subsection, 701.1.1 Vent and combustion air ducts, to read as follows:

701.1 Vent and combustion air ducts. Vent and combustion air ducts shall terminate a minimum of 36 inches above finished grade.

17. Section 804.3.4 Horizontal terminations is amended by changing Item 6 to read as follows:

Item 6. The bottom of the vent termination shall be located at least 36 inches above finished grade.

18. Section 805 Factory-Built Chimneys is amended by adding new subsections to read exactly as set forth in IBC Sections 718.6, 718.7, and 2113.22 as amended.

19. Section 903.3 Unvented gas log heaters is amended to read as follows:

903.3 Unvented gas log heaters. Unvented gas log heaters are prohibited.

20. Section 905 Fireplace Stoves and Room Heaters is amended by adding a new subsection, 905.4 Limitation on the type and number of devices, to read as follows:

905.4 Limitation on the type and number of devices is added to read exactly as set forth in IBC Section 2113.21 as amended.

21. Section 1208.1 General is amended by adding the following sentences at the end of the paragraph.

Hydronic tubing may be tested with a 50 psi air test for a minimum of 30 minutes. Assembled loop systems may be tested with a 50 psi air test for a minimum of 30 minutes.

(Ord. 38, Series 2019)